Details description
1.Purposes
3-Phase electronic active & reactive combined Kilowatt Hour Meter with high accuracy and reliability. It adopts international advanced low energy consumption large-scale IC and SMT Technology, all key components are of international famous brands with long service life, which prolongs service life of product greatly. It is capable of precisely measuring active power and Reactive power with rated frequency of 50 Hz or 60Hz in 3-Phase Power Supply Network, and replacing two common 3-Phase Kilowatt Hour Meters. The product is in accordance with all technical requirements in GB/T17215-2002, GB/T17882-1999 and DL/T645-1997 for 3-Phase electronic Kilowatt Hour Meter.
2. Functions and features
2.1 with standard RS485 port can transfer data in long distance. Can communication with PC by RS485, the communication protocol and data structure confirm to DL/T645-1997 standard, baud rate is 1200bps.
2.2 with active pulse and reactive pulse output, the pulse width is 80ms±20ms.
2.3 can measure active energy consume (kW.h) and reactive energy consume (kvar.h)
total active energy (kW.h) =positive active energy + reverse active energy;
total reactive energy (kvar.h) =positive reactive energy + reverse reactive energy.
2.4 3-Phase power supply. When 1-Wire (any one line in 3-Phase & 3-Wire Kilowatt Hour Meter) or 2-Wire (any two wires in 3-Phase & 4-Wire Kilowatt Hour Meter) is cut off, measurement accuracy still is ok
2.5 adopt advance energy meter integrate circuit, the data is saved in storage forever, lose voltage not lose data.
2.6 with phase-cut indication function. (for 3phase 3wire meter if Phase Ub is cut without indication)
2.7 Wide working temperature range;
2.8 High accuracy, active is class 1, reactive is class 2
3. Specification and main technical data
3.1 Specification/model:
| Model |
Specification |
Accuracy |
Pulse constant |
| DSS(X)855(3phase 3wire) |
3×100V |
3×1.5(6)A |
1.0/2.0 |
3200imp/kWh/kvarh |
| DTS(X)855(3phase 4wire) |
3×220/380V or3×57.7/100 |
3×1.5(6)A |
1.0/2.0 |
3200imp/kWh/kvarh |
| 3×5(20)A |
1.0/2.0 |
800imp/kWh/kvarh |
| 3×10(40)A |
1.0/2.0 |
400imp/kWh/kvarh |
| 3×15(60)A |
1.0/2.0 |
400imp/kWh/kvarh |
| 3×20(80)A |
1.0/2.0 |
200imp/kWh/kvarh |
| 3×30(100)A |
1.0/2.0 |
200imp/kWh/kvarh |
3.2 starting: active 0.004Ib(CT 0.002 In)(class 1)reactive 0.005Ib(CT 0.003 In)(class 2)
3.3 no-load running: when current circuit without current, in voltage circuit with 115% of rated voltage, the meter’s pulse output not more than 1.
3.4 Rated frequency:50Hz or 60Hz
3.5 Reference voltage (V): 3*57.7/100V or 3*220/380V or 3*100V
3.6 electric parameter:
normal working voltage: 0.9Un~1.1Un
limited working voltage: 0.8Un~1.15Un
voltage circuit power loss: ≤2W and 10VA
3.7 environment condition:
standard working temperature -30℃~+55℃
limited working temperature -40℃~+70℃
relative humidity ≤85%
3.8 shape size: 150mm*249mm*70mm
3.9 weight: 1.5kg
4. Appearance size and connections
4.1 Appearance size drawing

4.2 Assistant terminals connection (for reference)

4.3 Power supply terminals
CT (current transformer) type: 3X230/400V 3X1.5(6) A |
Direct connect type: 3X230/400V ≥3X5 (20) A |

|

|
|
|
CT (current transformer), PT (Potential transformer) type: 3X57.7/100V 3X1.5(6)A |
CT (current transformer), PT (Potential transformer) type: 3X100V 3X1.5(6) A |

|

|
|
|
Testing pulse interface |
|

|
|
Material object drawing:

|