TYPE: CJX2 Series AC Contactor
CJX2 series AC contactor is suitable for use in the circuit up to the rated voltage 660V AC 50Hz or 60Hz, rated current 95A, for making and breaking and frequent starting, controling the AC motor, combined with the auxiliary contact group, air delayer, machine-interlocking device, etc, it is combined into the delay contactor, mechanical interlocking contactor, star-delta starter, with the thermal relay, it is combined into the electromagnetic starter.
Characteristic
△Action machine is direct drive , contactor is double breaking contacts
△Combine function, can add accessories in each face except fixing face
△both side can add auxiliary contact group (F4-d1) or interlock machine.
△in up can add auxiliary contact group (F4 or F4-d2) or air time-delay head(YWLAD-T/R)
△in terminals of winding can add time-delay element etc.
■ Specification
Model |
Rated Working Current (A)
AC-3 380V |
Control power KW |
quantity of head |
220V |
380V |
415V |
440V |
660V |
3P+NO
or 3P+NC |
CJX2-09 |
9 |
2.2 |
4 |
4 |
4 |
5.5 |
CJX2-12 |
12 |
3 |
5.5 |
5.5 |
5.5 |
7.5 |
CJX2-18 |
18 |
4 |
7.5 |
9 |
9 |
9 |
CJX2-25 |
25 |
5.5 |
11 |
11 |
11 |
15 |
CJX2-32 |
32 |
7.5 |
15 |
15 |
15 |
18.5 |
CJX2-38 |
38 |
9 |
18.5 |
18.5 |
18.5 |
18.5 |
CJX2-40 |
40 |
11 |
18.5 |
22 |
22 |
30 |
3P+NO+NC |
CJX2-50 |
50 |
15 |
22 |
25 |
30 |
33 |
CJX2-65 |
65 |
18.5 |
30 |
37 |
37 |
37 |
CJX2-80 |
80 |
22 |
37 |
45 |
45 |
45 |
CJX2-95 |
95 |
25 |
45 |
45 |
45 |
45 |
3P: Three head Always-ON;
NO: one auxiliary head Always-ON;
NC: one auxiliary head Always-OFF
■ Specification of accessories
△F4 Auxiliary head group
Type |
Head quantity |
F4-10d2 |
NO |
F4-01d2 |
NC |
F4-11 |
NO+NC |
F4-11d2 |
NO+NC(Side fixing) |
F4-20 |
2NO |
F4-02 |
2NC |
F4-20d2 |
2NO(Side fixing) |
F4-22 |
2N0+2NC |
F4-40 |
4NO |
F4-04 |
4NC |
F4-31 |
3NO+NC |
F4-13 |
NO+3NC |
Air time-delay head
|
Type |
Time-delay range (s) |
time-delay head quantity |
Note |
YWLAD-T0 |
0.1~3S |
NO+NC |
Switch ON time-delay |
YWLAD-T2 |
0.1~30S |
YWLAD-T4 |
10~180S |
YWLAD-R0 |
0.1~3S |
Switch OFF time-delay |
YWLAD-R2 |
0.1~30S |
YWLAD-R4 |
10~180S |
Technical parameter
Standard: IEC60947-4, GB14048.4
| Type Parameter |
CJX2-09 |
CJX2-12 |
CJX2-18 |
CJX2-25 |
CJX2-32 |
CJX2-38 |
CJX2-40 |
CJX2-50 |
CJX2-65 |
CJX2-80 |
CJX2-95 |
Rated Working Current Ie (A) (AC-3) |
380V |
9 |
12 |
18 |
25 |
32 |
38 |
40 |
50 |
65 |
80 |
95 |
660V |
6.6 |
8.9 |
12 |
18 |
21 |
21.5 |
34 |
39 |
42 |
49 |
49 |
Promise heat Current Ith (A) |
25 |
25 |
32 |
40 |
50 |
50 |
60 |
80 |
80 |
125 |
125 |
Rated Working voltage Ue (V) |
690380 |
380 |
690380 |
Rated insulated Voltage Ui (V) |
690 |
AC-3
(6le,le) |
Electricity Life
(X104) |
100 |
100 |
100 |
100 |
80 |
50 |
80 |
60 |
60 |
60 |
60 |
Operate frequency
(time / Hour) |
1200 |
1200 |
1200 |
1200 |
600 |
600 |
600 |
600 |
600 |
600 |
600 |
AC-4
(6le,6le) |
Electricity Life
(X104) |
20 |
20 |
20 |
20 |
20 |
15 |
15 |
15 |
15 |
10 |
10 |
Operate frequency
(time / Hour) |
300 |
150 |
Rated Working Current le (A) |
380V |
3.5 |
5 |
7.7 |
8.5 |
12 |
13.9 |
18.5 |
24 |
28 |
37 |
44 |
660V |
1.5 |
2 |
3.8 |
4.4 |
7.5 |
13.9 |
9 |
12 |
14 |
17.3 |
21.3 |
Auxiliary Contactor |
Promise heat Current Ith (A) |
10 |
Electricity Life |
AC-15(360VA) |
Same with main Contactor life (AC-3) |
DC-13(33W) |
Min Loading |
6V 10mA |
Winding |
Rated Control voltage Us (V) |
24, 48, 110, 220, 380 |
Pick-up voltage |
0.85~1.10Us |
Release voltage |
0.2~0.75Us |
Coil power (VA) |
Pick-up |
76 |
76 |
76 |
110 |
110 |
110 |
230 |
230 |
230 |
230 |
230 |
Holding |
9.4 |
9.4 |
9.4 |
11 |
11 |
11 |
26 |
26 |
26 |
26 |
26 |
Machine life (X104) (time) |
1000 |
800 |
600 |
Terminals Connection wire
( mm2) |
conducting wire quantity |
1 |
2 |
1 |
2 |
1 |
2 |
1 |
2 |
1 |
2 |
1 |
2 |
1 |
2 |
1 |
2 |
1 |
2 |
1 |
2 |
1 |
2 |
Soft wire |
2.5 |
2.5 |
2.5 |
2.5 |
4 |
4 |
4 |
4 |
6 |
6 |
6 |
6 |
10 |
10 |
16 |
16 |
16 |
16 |
50 |
25 |
50 |
25 |
Hard Wire |
4 |
4 |
4 |
4 |
6 |
6 |
6 |
- |
10 |
10 |
10 |
10 |
10 |
10 |
25 |
- |
25 |
- |
50 |
- |
50 |
- |
Outline and fixing Size
△CJX2-09, 12, 18

Unit:mm
Type |
Amax |
Cmax |
C1 |
C2 |
|
class=unnamed1>Note:
C:CJX2
C1:CJX2+F4
C2:CJX2+YWLAD-T/R |
CJX2-09, 12 |
47 |
82 |
115 |
134 |
CJX2-18 |
47 |
87 |
120 |
139 |
△CJX2-25, 32, 38

Unit:mm
Type |
Amax |
Cmax |
C1 |
C2 |
|
Note:
C:CJX2
C1:CJX2+F4(orF4-d2) C2:CJX2+YWLAD-T/R |
CJX2-25 |
59 |
97 |
130 |
149 |
CJX2-32 |
59 |
102 |
135 |
154 |
CJX2-38 |
59 |
102 |
135 |
154 |
△CJX2-40, 50, 65, 80, 95

Unit: mm
Type |
Amax |
Cmax |
C1 |
C2 |
|
class=unnamed1>Note:
C:CJX2
C1:CJX2+F4(or F4-d2)
C2:CJX2+YWLAD-T/R |
CJX2-40,50,65 |
79 |
116 |
149 |
168 |
|
CJX2-80,95 |
87 |
127 |
160 |
179 |
|
Connection Drawing:
 |